Tool box
- Calibers
-
Horned gaps
of two phases for 13,2 KV - Dimensions and weights
- Rated currents
Calibers
Mono phase current | Three-phase current | |||||
---|---|---|---|---|---|---|
Power | 13,2 KV | 33 KV | 13,2 KV | 33 KV | Power | |
In Fu | In Fu | In Fu | In Fu | |||
5 | 0.38 1.45 | 0.22 0.45 | - - | 5 | ||
10 | 0.76 0.9 | 0.44 0.57 | - - | 10 | ||
15 | 1.2 1.6 | 0.48 0.57 | 0.7 0.9 | - - | 15 | |
20 | - - | - - | 1.1 1.6 | 0.44 0.57 | 20 | |
0 | - - | - - | 1.95 2.1 | 0.7 0.9 | 0 | |
63 | - - | - - | 2.8 3.9 | 1.1 1.6 | 63 | |
100 | - - | - - | 4.35 5 | 1.75 2.1 | 100 | |
160 | - - | - - | 7 9.7 | 2.8 3.9 | 160 | |
200 | - - | - - | 8.7 9.7 | 3.5 3.9 | 200 | |
250 | - - | - - | 10.9 14.6 | 4.4 5 | 250 | |
315 | - - | - - | 13.7 14.6 | 5.6 7.2 | 315 | |
400 | - - | - - | 19.5 22 | 7 9.7 | 400 | |
500 | - - | - - | 21.8 27 | 8.8 9.7 | 500 | |
630 | - - | - - | 27.6 35 | 11.2 14.6 | 630 | |
800 | - - | - - | - - | - - | 800 | |
1000 | - - | - - | - - | - - | 1000 |
Horned gaps of two phases for 13,2 KV
Level | Distances | Level of protection |
Table of distance calibrated ds and sl |
---|---|---|---|
1 |
ds= 14mm
sl=14mm a=10mm cl= 9,8mm d=6mm |
0%: 60 KV 100%: 65 KV |
The discharge voltage of a gap essentially depends on the distance between the electrodes and the layout and distance between the live parts and the ground nearby. Level 1 must be used in the absence of non-lineal dischargers and Level 2 when they are installed. |
2 |
ds= 20mm
sl=20mm a=10mm cl= 17.3mm d=6mm |
0%: 73.6 KV 100%: 85 KV |
Dimensions and weights
RURAL MONO-PHASE CURRENT AND THREE-PHASE CURRENT | ||||||||
---|---|---|---|---|---|---|---|---|
Power | LEAKS IN A VACUUM | LEAKS IN CTO.CTO. | VOLTAGE IN CTO. CTO. | Height | Width | LENGTH | OIL VOLUME | TOTAL WEIGHT |
Kva | w | w | % | mm | mm | mm | Lts | kg |
MONO- PHASE CURRENT - RELATION 7620 ± 5% / 231 V | ||||||||
5
10 16 |
30
45 60 |
160
290 390 |
4.5
4.5 4.5 |
820
860 920 |
420
420 460 |
460
460 530 |
25
25 33 |
4.5
4.5 4.5 |
MONO- PHASE CURRENT - RELATION 13200 ± 5% / 231 V | ||||||||
5
10 16 |
30
45 60 |
160
290 390 |
4.5
4.5 4.5 |
820
860 920 |
420
420 460 |
460
460 530 |
25
25 41 |
4.5
4.5 4.5 |
MONO- PHASE CURRENT - RELATION 13200 ± 5% / 400 - 231 V | ||||||||
10
16 25 40 63 |
80
100 140 180 230 |
340
550 650 1050 1450 |
4.5
4.5 4.5 4.5 4.5 |
1280
1300 1320 1370 1460 |
460
560 640 800 950 |
530
530 530 600 600 |
68
75 80 118 124 |
190
215 250 340 430 |
Of distribution | ||||||||
---|---|---|---|---|---|---|---|---|
Power | LEAKS IN A VACUUM | LEAKS IN CTO.CTO. | VOLTAGE IN CTO. CTO. | Height | Width | LENGTH | OIL VOLUME | TOTAL WEIGHT |
Kva | w | w | % | mm | mm | mm | Lts | kg |
Relation 13200 ± 2 x 2.5 / 400 - 231 V | ||||||||
100
160 200 250 315 400 500 630 800 1000 |
350
500 600 700 850 1020 1200 1450 1750 2100 |
1750
2500 3000 3500 4250 5100 6000 7250 8750 10500 |
4
4 4 4 4 4 4 4 5 5 |
1400
1450 1470 1640 1680 1760 1770 1800 1800 1850 |
780
870 830 980 950 1030 1060 1150 1240 1240 |
1250
1350 1410 1400 1600 1650 1700 1850 1960 2000 |
170
210 220 260 295 350 410 460 530 670 |
660
910 950 1160 1320 1620 1850 2200 2650 2880 |
Rated currents
TRANSFORMERS OF 7,62/0,231 Kv | ||
---|---|---|
POWER (Kva) | Primary (Amp) | Secondary (Amp) |
5
10 16 25 |
0,65
1,31 2,10 3,28 |
22,00
44,00 69,20 108,20 |
TRANSFORMERS OF 13,2/0,400-0,231 Kv | ||
---|---|---|
POWER (Kva) | Primary (Amp) | Secondary (Amp) |
5 (13,2/0,231)
10 (13,2/0,231) 16 (13,2/0,231) 10 16 25 40 63 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3000 |
0,37
0,75 1,20 0,43 0,70 1,10 1,75 2,75 4,37 5,46 7,00 8,74 10,93 13,70 17,50 21,86 27,50 35,00 44,00 55,00 70,00 88,00 110,00 131,00 |
22,00
44,00 69,50 14,50 23,10 36,10 58,00 91,00 145,00 180,00 231,00 289,00 361,00 455,00 578,00 722,00 910,00 1155,00 1445,00 1800,00 2310,00 2890,00 3601,00 4330,00 |
TRANSFORMERS OF 33/0,400-0,231 Kv | ||
---|---|---|
POWER (Kva) | Primary (Amp) | Secondary (Amp) |
25
40 63 100 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3000 |
0,43
0,70 1,10 1,75 2,80 3,50 4,37 5,51 7,00 8,74 11,02 14,00 17,50 21,86 28,00 35,00 43,70 52,40 |
36,10
58,00 91,00 145,00 231,00 289,00 361,00 455,00 578,00 722,00 910,00 1154,00 1445,00 1800,00 2310,00 2890,00 3601,00 4330,00 |